    Product Description

    Prefabricated modular Air Shower Unit used for removing surface particle from personnel prior to entering a contamination controlled environment. Air shower are constructed as per ISO 14666.

    Specification

    Cleanliness

    ISO 8

    Material of Construction

    Main Structure do with MS Powder Coated / S.S. 304 construction

    Inside Working Area : MS Powder Coated  / S.S 304

    Bottom do with Aluminum Checker Plate

    Both Side Entry / Exit Door : S.S / GI Powder Coated duly Double Skinned

    Velocity at Nozzle

    15 ± 5 M/S

    Blower Assembly

    Statically and dynamically balanced Motor & Blower, designed for supply of sufficient capacity and static pressure to take care of airflow

    Doors

    Automatic swing, micro-processor controlled electromagnetic inter locking doors with glass panels. (Comprising with Door Closure, ‘D’ Handle, Ball Bearing Hinges)

    HEPA Filter

    HEPA Filters down to 0.3mic. particulate at an efficiency of 99.999% (H14) duly tested on PAO tested

    Make-up Air Filter

    Pre-Filter down to 5mic. Particulate at an efficiency of 95% (EU5) enclosed in aluminum frame with epoxy sealing (Washable Type)

    Return Air Filter

    Pre-Filter Filter down to 5mic. Particulate at an efficiency of 95% (EU5) enclosed in aluminum frame with epoxy sealing (Disposable Type)

    Nozzle

    All Nozzles with S.S. 304

    Door Interlocking

    Door Opening with Solid State Electronic Inter Locking Mechanism

    Power supply

    440 V, 50Hz, Three Phase

    Operation Sequence

    Detail of logic Sequence:

    First Cycle of operation : –

    When D1 & D2 are  Closed  (Both Door are in locked condition)

    Blower in off condition

    When D1 is Opened  (Door D2 gets locked condition)

    Blower in off condition

    When D1 is closed  (Door D2 still in locked condition)

    Blower will be on when both doors are in locked condition

    Blower motor (As per timer setting) gets off and then Door D2 gets opened / unlocked, D1 in locked condition

    Door D2 is closed condition

    Door D1 / D2 gets opened / unlocked

    At a time only one door can opened

    Emergency Stop/Unlock Button provided at Entry / Exit/ Inside chamber


    Operation Sequence:- First Cycle of operation: 

    • When D1 & D2 are  Closed  (Both Door are in locked condition), Blower in off condition
    • When D1 is Opened  (Door D2 gets locked condition), Blower in off condition
    • When D1 is closed  (Door D2 still in locked condition), Blower will be on when both doors are in locked condition
    • Blower motor (As per timer setting) gets off and then Door D2 gets opened / unlocked, D1 in locked condition
    • Door D2 is closed condition
    • Door D1 / D2 gets opened / unlocked
    • At a time only one door can opened
    • Emergency Stop/Unlock Button provided at Entry / Exit/ Inside chamber

     

    Trade Information
    • Cheque
    • 20 Per Month
    • 3 Week
    • Yes
    • If order is confirmed we will reimburse the sample cost
    • As Actual
    • Africa, Middle East, Asia
    • All India
    • ISO 9001 - 2015 NSIC
    Contact Us

    69/70, Axar Industrial Park, B/h Amba Estate, Vinzol Patiya,Vatwa GIDC, Near Hathijan Circle , Ahmedabad, Gujarat, 382445, India
    Phone :+918045479501